Dran-View 6 User Guide
Compare harmonics against limits
Advanced
Category
Enterprise
Edition
Only
This option allows you to compare
harmonics against your own or pre-
defined limits. A set of pre-defined
limits is available when installing Dran-
View. These files have the extension
.DLM and can be loaded using the
“Open” button. The current settings can
be saved using the “Save” button.
The Report Writer will create a
PASS/FAIL report for the selected
harmonics.
Description This exit-box should contain a brief description of the limits
entered. The description will be included in the final page.
Cumulative
threshold (1-
100%)
This edit-box should contain a statistical value between 1-
100%. Most power quality standards include information about
this number; usually 95% or 100% is used. If a value other
than 100% is used, some fluctuations are filtered out. A 95%
value means that the worst (highest) 5% is excluded.
Planning level
(1-500%)
This edit-box allows you to scale the limits by the percentage
given. Typically this value is set to 100%, which means that
the limits are not modified before comparison.
Unit This combo-box contains the selection of “I” (current
harmonic) or “V” (voltage harmonic).
Harm This combo-box allows you to select what harmonic number to
analyze. Available selections include THD, DC, FND, H02-
H50.
Limit This edit-box contains the limit to compare against. If this field
is blank or 0.0, the row will not be part of the comparison.
Scale This combo-box allows you to select if the harmonic is in
“Abs” (volts or amps unit) or “%FND” (normalized to
fundamental).
Vue de la page 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 217 218