Dranetz Guide Guide de l'utilisateur Page 119

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 218
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 118
119
Dran-View 6 User Guide
10.13.2. Symmetric Components Page
Symmetrical
Components
Setup Page
Voltage/Current
These combo boxes contain possible harmonic scaling options.
"Absolute" will not scale the symmetric components. They will
be displayed as volts/amps if they were not measured as a
percentage. “% of Positive Component” scales each value
towards the positive component at the same frequency. This is
also known as the unbalance factor. “% of Positive Component
FND” scales each value towards the value of the positive
component at the fundamental frequency.
These settings will also affect the instrument-generated
symmetric components.
Phase angle
normalization
This option allows you to choose how phase angles should be
normalized. The channel or point used for normalization always
has a value of zero at all points.
Vue de la page 118
1 2 ... 114 115 116 117 118 119 120 121 122 123 124 ... 217 218

Commentaires sur ces manuels

Pas de commentaire