Set RMS Diff Transients – use to set the rms distortion
waveshape limit. The rms deviation algorithm subtracts the same
point-on-wave sample values from previous to present cycle then
calculates the rms value of the deviation over an entire cycle. If
this value exceeds the threshold, then a trigger occurs.
Set High Frequency Transients – the high speed sampling
analog board installed in Dranetz HDPQ Xplorer enables it to
detect and capture transients as small as 1 microsecond in
duration. This transient detection algorithm is only available on
the Xplorer.