DB-PX5 - PowerVisa 440® / PowerGuide® 4400 / PowerXplorer® PX5 Op. Skills
© 2006-2010 by PowerCET Corporation. All rights reserved. (100616)
47
©2006-2008 PowerCET Corporation. All rights reserved.
93
If applicable, Press: Group
A B C to simplify setup
Press the threshold
parameter (High, Low, Very
Low) to change, enable or
disable threshold values
High limits must be at least
.1 higher than Low limits, or
the entered value will not be
accepted.
Press: % of Nominal to use
percentages instead of amps
Press the other tabs to set
other channels
Press: Next
Wizard Setup: RMS Variation Limits
115A
©2006-2008 PowerCET Corporation. All rights reserved.
94
Choose the number of cycles of
RMS samples to record for RMS
Summaries
Choose the number of cycles
waveforms to capture for
Waveform Capture summaries—
recommend making value same as
RMS Summary cycles above.
These are two separate captures
stored into the database
Enable/Disable Waveform Capture
Press: Finish to return to the
advance options screen
Wizard Setup: RMS Variation & Waveform Capture
Note: PX5 & 4400 have 10,000-
cycles post-trigger capture.
PowerVisa 440 is limited to 100-
cycles post-trigger.